M/V Rystraum - Provision Refrigeration Repair

BreezeMarine engineers inspected, serviced and repaired the provision refrigeration system aboard M/V Rystraum at the Port of Pori, Finland. The initial inspection took place on 11 August 2026.

Challenge

The provision refrigeration system keeps the vessel’s food stores at temperature, so any loss of performance has to be found and fixed quickly.

The initial inspection showed the plant was short of refrigerant. Diagnostics traced the loss to leaks on the high-pressure side and the hot gas lines, and found a defective solenoid valve and thermostatic expansion valve.

Engineering Solution

  1. Checked operating pressures and temperatures and ran system diagnostics.
  2. Adjusted the evaporating pressure regulators and thermostatic expansion valves.
  3. Cleaned the suction filters and inspected the solenoid valves.
  4. Topped up 2 kg of R407F refrigerant.
  5. Repaired refrigerant leaks on the high-pressure side and hot gas lines and serviced the affected connections.
  6. Replaced the defective solenoid valve and thermostatic expansion valve.
  7. Leak-tested, evacuated and recharged the system.
  8. Commissioned the plant and verified operating pressures, temperatures and evaporator performance.

Customer

Utkilen AS

Vessel

M/V Rystraum

Vessel type

Chemical/Oil Products Tanker

Equipment

Provision Refrigeration System, R407F

Scope

Inspection, Servicing and Leak Repair

Turnaround

2 Visits